top of page
7001 pic1.jpg

or call
(913) 927 6144

BI-PARTING SLIDING COOLER / FREEZER DOOR

FEATURES:

  • Easy opening - Wide Wheel Spacing and smoth Track design makes opening effortless.

  • All Stainless Steel Door Capping, Hardware & Track Angle 

  • Made to custom-designed applications

  • USDA approved

Therm L Tec'sBi_Parting Horizontal Slide Door is by far the simplest and most fundamental door in the market for the last 30 plus years. When dependability is your primary concern, simple operation is very important. Therm L Tec's electric bi-parting sliding door has an absolute minimum of moving parts. Driven by a geared belt similar to the serpentine belt in your car means ongoing lubrication maintenance is eliminated. An eight foot wide door can be programmed to open in 1 second. This is unmatched by conventional door manufacturers and stands alone as the fastest operating door in the industry. The result is increased productivity, reduced energy loss and decreased maintenance cost due to door damage.

Utilizing the fast opening "state of the art" S.S.T. operator, this bi-parting slide door is capable of opening faster then our competitor's door of the same size.

Options: 

  • 12 W / foot heat in doors and bottom sweep, additional heat in door frame available (total 24 W / foot heat)

  • Insulated vision panel (Heated on Freezer doors)

  • Flush Sill or High Sill

  • Meat Rail Provision

  • Pad Lock with Emergency Egress from inside

  • Stainless Steel Kick Plates

  • Vision Panels

  • High R Value

  • Full Caustic Washdown 

Standard Sizes (Custom options available)​:

  • Height - 7' - 24'

  • Width - 7' - 20'

  • Thickness - 4", 6"

Door Details
Electric Operated Bi-PartingSliding Door

7001 pic2.jpg

Door Details
Manually Operated Bi-parting Sliding Door

7000 pic2.jpg

Specifications:

BI-PARTING COOLER / FREEZER DOORS
DIVISION 8 | SECTION 8325

PART  1 [ GENERAL ]

1.01 | SCOPE

Work required under this section shall include the furnishing of all labor, materials, tools and equipment to complete insulated door work as detailed on drawings or as specified herein.

1.02 | SYSTEM DESCRIPTION

All doors, door casings shall be fully clad on all exposed surfaces with paint, white embossed or flat 26ga G90 galvanized steel. All hardware shall be protected against corrosion. Doors with provision for locking shall have safety release on opposite site.

1.03 | SUBMITTAL

In Compliance with specification requirements, submit shop drawings including all information required for complete installation, head jamb and sill conditions and electrical requirements.

1.04 | QUALITY ASSURANCE

Doors shall be installed in accordance with the architects plans and specifications and door manufacturer's written instructions, drawings and recommendations.

1.05 | DELIVERY, STORAGE & HANDLING

Each Door shall be adequately crated to protect door from damage during shipment and handling. Each crate shall be marked with door identification number. Inspect door for damage at time of receipt. Storage of door at jobsite to be protected from weather. 

1.06 | WARRANTY

Doors shall be warranted against defective materials and workmanship for a period of one year.

PART 2 [ PRODUCTS ]

2.01

This specification is written with Therm-L-Tec, Series 7000 & Series 7001 insulated doors as basic performance standards. No substitution will be considered unless approved in writing by the architect.

2.02 | MANUFACTURED UNITS

  1. Provide Manually or Electrically operated horizontal sliding cooler / freezer doors ( flush sill, high sill optional ) including casings and track header.Inverted V UHMW track mounted on Stainless Steel angle; heavy duty trolleys with sealed-in grease bearings; bulb type neoprene or silicone rubber seals at head and sides, wiper gasket at sill. Door size and panel thickness as called for on drawings. Door panels to be free of wood; face casings and jamb to be wood, metal clad. Perimeter of door panel encased in 18ga Stainless Steel channel. Doors to be powered by SST electric Operator 1/2 HP enclosed 3 phase Motor. Belt drive. NEMA 4 control box with inverter, logic board, 24 Volt Control Cirucit and adjustable Limit Laser Sensors mounted on header. Header is factory pre-assembled. Full Height instant reversing edge. Furnished with two pull cord switches. 

 

2.03 | ACCESSOIRS / OPTIONS

  1. Provide U.L. approved perimeter heat cable on freezer doors.

  2. High Sill

  3. Deep Jambs, Back Trim, Mirror Image Header

  4. Padlocking with Emergency Inside Release

  5. Optional Cladding Material

  6. Vision Panel (heated on Freezer Door)

  7. Kick Plates

  8. Alternate types of actuating devices available

PART 3 [ EXECUTION ]

3.01 | INSTALLATION

  1. Install doors in compliance with manufacturer's instructions and final shop drawings. Mounting surface for vertical casings and track header shall be set true, plumb, level, square and shall be shimmed and securely anchored in place with sufficient fasteners to support weight of door. Caulk at frame / wall juncture.

  2. Power connections to operator, heater cable & pull cord switches by electrical contractor. Install factory wired door assembly (heater cable junction box on freezer door) following manufacturer's instructions and local electrical codes. After field connections have been made to electrical service, test for proper operations.

 

3.02 | ADJUSTING AND CLEANING

  1. When door panels are hung and electrical connections completed, check for mechanical and electrical operation and uniform gasket sealing with manufacturers installation instructions.

  2. Clean all doors of excess sealant, grease, stains, fingerprints and construction dust.

bottom of page